■ Discontinued: December 28, 2022 |
||
Two MKY37 ICs mounted, HLSB-37DI32A is a general-purpose input slave board of HLS family which mounts two MKY37 ICs. |
Item | Specifications | ||||
---|---|---|---|---|---|
HLS device | MKY37 × 2 pc | ||||
HLS communication method | Full-duplex /Half-duplex | ||||
HLS communication rate | 12/6/3 Mbps (Rate can be set by DIP switch.) | ||||
HLS termination resistor | 100 Ω (Enable/Disable can be selected.) | ||||
General-purpose input method and number of inputs |
Current source type by photocoupler isolation: 32 inputs | ||||
General inputs ON/OFF delay | 100µs or lower | ||||
LED | POWER MON DI |
(Green) (Green) (Green) |
+5.0 V MKY37 DIN data |
Power supply MON 32 pcs |
|
Switch | HLS termination setting switch HLS SA setting switch HLS communication rate setting switch HLS communication mode setting switch |
||||
Connector |
HLS communication connector (RJ45 type) × 2 pcs General-purpose input connector (MIL type) × 2 pcs Power supply connector (SPTA 1/ 4-3,5 PHOENIX) |
||||
Size | 64 mm × 130 mm | ||||
Weight | 70 g | ||||
Operating temperature |
Temperature: 0℃ to 55℃ Humidity: 0% to 90% (With no condensation.) |
||||
Storage temperature |
Temperature: -20℃ to 65℃ Humidity: 0% to 90% (With no condensation) |
||||
External circuit power supply | 24 V DC +10%, -15% | ||||
Internal circuit power supply | DC/DC converter isolates 24 V DC external power supply into 5.0 V DC internal operating voltage. |
||||
Consumption current (24 V DC power supply) |
250 mA or lower |